The leading ignition protection type is crucial for the electrical connection of a pressure sensor with explosion protection. It generally does not necessarily have to be the main one with the stricter requirements. This applies, for instance, for the UHP pressure transducers of the WU series from WIKA. They have been designed for used in semiconductor production.
Explosion protection can be an indispensable safety precaution there. For the reason that the substances necessary for manufacturing include highly flammable gases. Consequently, you will find a risk of an explosive atmosphere forming.
Explosion protection concept
UHP pressure transducers for such processes must be made with the corresponding safety. As well as their small design and specific process connections, the models WUC-1x and WU-2x have a comprehensive explosion protection concept. The marking of the instruments provides information on this:
II 3G Ex ec ic IIC T6/T5/T4 Gc X
The abbreviations listed inside them mean, in more detail:
II 3G:
Equipment group 2 (all areas except mining), can be used in zone 2 (rare and short-term Ex atmosphere).
Ex ec ic:
Ignition protection types ?ec? (increased safety) and ?ic? (intrinsically Surprised ).
?Ex ec? has replaced the ignition protection type ?Ex nA? (non-sparking) because the start of 2022. However, this will not affect the Ex concept of the instruments.
IIC:
Explosion group (here: gases, resistive ignition energy of 40 �J, ideal for hydrogen/acetylene).
T6/T5/T4:
Temperature classes. T6 as the highest requirement means a maximum permissible surface temperature in the Ex environment < 85 �C (max. surface temperature of the WUC-1x and WU-2x: 40 �C).
Gc:
?Equipment Protection Level? (EPL) for zone 2 per IEC 60079-0
X:
Specific requirements which are listed in the operating instructions (for example, the best mating connector).
?ec? is the leading ignition protection type
It really is noticeable that the marking contains two ignition protection types. However, only one is pertinent for the electrical connection: the leading ignition protection type. In the case of the pressure transducers from the WU series, here is the Ex ec (Ex nA up to 2022) mentioned first and not the stricter Ex ic. This can also be seen in the bond values in the data sheet and operating instructions. Only the specification of the utmost supply voltage UN = 30 V, that is also stated in the IECEx certificate, is pertinent here.
What does the classification ?Ex ic? stand for? It only applies to the potentiometer of the transducer. The resistive component has an intrinsically safe circuit and may therefore be adjusted to improve zero drift during operation. In their overall form, the WU models do not require an intrinsically safe circuit. However, they need to never be disconnected from the circuit during operation or when an Ex atmosphere is present.
Note
More info on the WUC-1x and WU-2x UHP pressure transducers and about hydrogen are available on the WIKA website. Assuming you have any questions, your contact will gladly assist you to.